VCG202/EN M/H11
 
 
Technical 
 
The relay will only respond to the commands via serial port if link SD2=1.  
Setting SD2=0 inhibits all remote commands over the serial port.  
The following cell locations are allocated to store three levels of loadshedding/boosting in 
the CONTROL column of the menu system.  
LEVELS  Cell Location 
Level 1  030E 
Level 2  030F 
Level 3  0310  
The following truth table then applies:  
COURIER COMMAND  SELECT  
Level 0  None 
Level 1  Select level 1 setting 
Level 2  Select level 2 setting 
Level 3  Select level 3 setting  
7.6.2  Local control of loadshedding/boosting 
Local loadshedding/boosting control of the relay are via using the opto inputs assigned in 
input mask.  The three levels can be selected by energising one of the three opto input 
channels as required by the user.  If more than one opto inputs are energised at any one 
time then the relay acts on the setting nearest to 0.  
For example, if 
Level1 = 3 % and Level 2 = +9 %, then level 1 is selected OR 
Level1 = 3 % and Level 2 = –3 % then level 2 is selected. The –ve setting has priority 
over the +ve setting if both values are equally nearest to 0.  
The following cell locations are assigned in the input masks.  
LEVELS  Cell Location 
Level 1  0707 
Level 2  0708 
Level 3  0709