Manual
 
 
KVCG202/EN M/H
 
 
7.4  Data for system integration 
7.4.1  Relay address 
The relay can have any address from 1 to 254 inclusive.  Address 255 is the global 
address that all relays, or other slave devices, respond to.  The Courier protocol specifies 
that no reply shall be issued by a slave device in response to a global message.  This is 
to prevent all devices responding and causing contention on the bus.  
The relay is supplied with its address set to 255 to ensure that when connected to an 
operational network they will not have a conflicting address with another device that are 
already operational.  To make the new devices fully operational they must have their 
address set.  The address can be changed manually by entering the password and 
changing the address by the setting change method via the user interface on the front of 
the relay. 
Alternatively, if the software running on the PC supports “auto-addressing”, the relay 
address can be set to “0” and the auto-addressing feature of the PC software turned on.  
The relay will then be automatically set to the next available address on the bus. PAS&T 
software supports both these feature. 
If the address is 255, or unknown, the device address can be changed by sending a new 
address, in a global message, to a device with a particular serial number.  This method is 
useful for devices that are not provided with a user interface with which to read the or 
change the current address and is supported by both PAS&T, ACCESS and CourierCom. 
7.4.2  Measured values 
Any measured value can be extracted periodically by polling the relay.  Measured values 
are stored in the menu locations under column heading MEASURE. 
7.4.3  Status word 
A status byte is contained in every reply from a slave device.  This is returned by the 
relay at the start of every message to signal important data on which the Master Station 
may be designed to respond automatically.  
The flags contained are: 
Bit 0 – 1  = Not used   
Bit 1 – 1  = Plant status word changed       
Bit 2 – 1  = Control status word changed       
Bit 3 – 1  = Relay busy, cannot complete reply in time   
Bit 4 – 1  = Relay out of service         
Bit 5 – 1  = Event record available for retrieval     
Bit 6 – 1  = Alarm LED lit        
Bit 7 – 1  = Control LED lit         
Bits 6 and 7 are used to mimic the alarm and control indication on the frontplate of the 
slave devices.  They cannot be used extract fault and alarm information from a slave 
device because they cannot be guaranteed to be set for a long enough period to be 
identified.  
Bits 5 enable the master station to respond automatically and extract event records, if 
they are so programmed so to do.  
7.4.4  Plant status word 
The plant status word can be found in menu cell 000C.  It is used to transport plant status 
information over the communication network.  This feature is not used on KVGC202 
relay.