K
VCG202/EN M/H11
Technical
Manual
KVGC202
Cell Text Status Description
3
IL> blk
1 = block for excessive load current
4 Total opsBlk 1 = block for excessive number of operations
5 Freq opsBlk 1 = block for frequent operation
6
Irev blk
1 = block operation for reverse current flow
7 Runaway blk 1 = block for tap change runaway
8
IL<BLK
1= block for insufficient current
0402 V<< SET Under voltage total inhibit level (% of Vs)
0403 V< SET Over voltage blocking limit
0404 V> SET Under voltage blocking limit
0405 t V< V> SET Under/over voltage blocking timer
0406 tFAIL> SET Total time outside dead band to=failure
0407
Ic>
SET Excessive circulating current threshold
0408
tIC
SET Excessive circulating current time delay
0409
IL>
SET Line overcurrent threshold
040A
IL<
SET Line undercurrent threshold
040B TpAvail SET Total number of taps available
040C TP> SET Upper tap alarm limit
040D TP< SET Lower tap alarm limit
040E total ops> SET Total number of tap change operations
040F ops/tP> SET Number of tap changes allowed in time tP
0410 tP SET Time period tP
0411 Display SET Default display required
0412 tTest Relay SET Relay test hold timer
3.3.10 Control 2
Cell Text Status Description
0500 CONTROL (2) READ Software links that are used to select the available
optional group 2 control functions.
0501 CTL Links PWP Function links
0
1 1= tINV 1 = Inverse time delay = dV.DT/(V ±Vs)
0502 CT Ratio PWP Line Current Transformer overall ratio
0503 VT Ratio PWP Line Voltage Transformer overall ratio
0504
In
PWP Rated current winding of relay (1A or 5A)
0505 Vs SET Set value of remote regulated voltage
0506 DV SET Dead band = ±dV
0507
Vc(volt/In)
SET Circulating current compensation
0508
Vr(volts/In)
SET Resistive LDC compensation
0509
Vx(volts/In)
SET Reactive LDC compensation (= reverse)
050A pf Angle SET Low power factor LDC compensation (90°)
050B tINIT DT SET Initial definite time delay