VCG202/EN M/H11
 
 
Technical 
 
Setting  Symbols  KVGC adjustment range   In steps of 
Tap change indication time  t Tap change  1 – 3 secs  0.1 secs 
 
5.1.1  Setting voltage (Vs) 
The setting voltage can be selected between 90 and 139V in 0.1 volt steps.  
The relay compares the system input voltage with this setting voltage and provides raise 
or lower signals to the tap changer to control the system voltage to be within the set 
deadband limits. 
5.1.2  Deadband (dVs) 
The deadband limits are defined as dVs % of Vs setting and are dependent on the tap 
step increment of the regulating transformer.  Typically, dVs % = ±1% for an average tap 
step increment of 1.4% on the transformer.  The deadband can be set between 0.5% to 
20% of Vs. 
5.1.3  Initial time delay setting (tINIT)  
The time delay to initiate a tap change sequence is set by the initial time delay setting 
between 0 and 300 seconds.  A software function link (CTL link 2) determines setting of 
either definite or an inverse time characteristic. 
Selection of a ‘definite’ initial time delay provides a fixed definite time delay before 
initiating a tap change and is independent of the voltage deviation.  Whereas, selection of 
an ‘inverse’ characteristic gives a time delay inversely proportional to the voltage 
deviation from the setting voltage, Vs.  
For inverse characteristic the initial time delay setting defines the operating time delay at 
the edge of the deadband, N=1.  Larger voltage deviations give corresponding faster 
operating times as shown by the inverse characteristic in Appendix 1.  The general 
expression for inverse time curve: 
    t  = k + [(initial time delay setting) x (1/N)]  
where   k  = 0.5  for initial time delay setting -20s 
      = 0  for initial time delay setting >20s 
N indicates % deviation from Vs in multiples of dVs % and is calculated as: 
N =  
Vreg - Vs
Vs 
*100
 dVs %
 
 
where   Vreg  = Voltage to be regulated 
Vs  = Voltage setting 
dVs %  = Dead band 
5.1.4  Inter-tap delay (tINTER) 
Where a multiple tap change sequence is required to bring the voltage back to within the 
deadband limits then the time delay between successive tapping outputs can be set 
between 0 and 120 seconds.  This is normally set to be slightly longer than the operating 
time of the tap changer mechanism.  
The inter-tap delay starts after the first tap pulse has elapsed.  When the initial time has 
elapsed the output continues to give pulsed closure for tap pulse duration at intervals set 
by the inter-tap delay.  Setting the inter-tap delay to 0 seconds results in a continuous 
output indicated by continuously illuminated ‘Control LED’.