VCG202/EN M/H11
 
 
Technical Manua
KVGC20
 
3.4.14
  Setting output masks  29 
3.4.15  Resetting values  29 
3.4.16  Resetting CONTROL LED indication  29 
3.5  External connections  29 
3.5.1  Auxiliary supply  30 
3.5.2  Logic control inputs  31 
3.5.3  Analogue inputs  32 
3.5.4  Output relays  32 
3.5.5  Setting the relay with a PC or Laptop  32 
3.6  Alarm flags  33 
4.  APPLICATION OF CONTROL FUNCTIONS  34 
4.1  Configuring the relay  34 
4.2  Changing the configuration of the relay  34 
4.2.1  SYSTEM DATA (SD)  34 
4.2.2  Logic links (LOG)  35 
4.2.3  Control links (CTL)  36 
4.2.4  Default output relays  36 
4.3  Setting group selection  36 
4.4  ApplicatIons  37 
4.4.1  Introduction  37 
4.4.2  Basic requirements  37 
4.4.3  Operating time delay  37 
4.4.3.1  Initial delay (tINIT)  38 
4.4.3.2  Definite/Inverse time characteristics  38 
4.4.3.3  Intertap Delay  39 
4.4.3.4  Tap Pulse Duration (tPULSE)  39 
4.4.4  Operating Sequences  39 
4.4.4.1  Method 1  39 
4.4.4.2  Method 2  39 
4.5  Line drop compensation  40 
4.6  Auto, manual and remote operation modes  41 
4.6.1  Remote change of operating mode  42 
4.6.2  Manual change of operating mode via logic input  42 
4.7  Paralleled transformers  42 
4.7.1  Master-Follower schemes  43 
4.7.2  Instability of individually controlled parallel transformers  44 
4.7.2.1  Runaway  44 
4.7.2.2  Effect of circulating current on LDC  45 
4.7.3  Negative reactance compounding  47 
4.7.4  Circulating current control  50 
4.7.4.1  Independent/parallel control  51 
4.7.4.2  Circulating current control with LDC  52 
4.8  Supervision functions of a VRR  58 
4.8.1  Runaway protection  58 
4.8.2  Undervoltage detection (V<)  58 
4.8.3  Undervoltage blocking (V<<)  59 
4.8.4  Overvoltage detection (V>)  59 
4.8.5  Overcurrent detection (I
L
>)  59 
4.8.6  Undercurrent detection (I
L
<)  59 
4.8.7  Circulating current detection (IC>)  59 
4.8.8  Reverse current detection (I rev)  59 
4.9  Tap position indication  59