VCG202/EN M/H11
Technical
[F]long – means press F key and hold for longer than 1 second.
[F]short – means press F key and hold for less than 1 second.
[F] – means press the F key length of time does not change the response.
[0]long – on perform a reset function when a resettable cell is displayed.
3.4.2 To enter setting mode
Give the [F] key a momentary press to change from the selected default display and
switch on the back-light; the heading SYSTEM DATA will be displayed. Use the [+] and
[–] keys, or a long press of the [F] key, to select the column containing the setting, or text
that is to be changed. Then with the [F] key step down the column until the contents of
that cell are displayed. Press either the [+] or [–] key to put the relay into the setting
mode. Setting mode will be indicated by a flashing cursor on the bottom line of the
display. If the cell is read-only, or password protected, then the cursor will not appear
and the relay will not be in the setting mode.
3.4.3 To escape from the setting mode
IMPORTANT! If at any time you wish to escape from the setting mode without making a
change to the contents of the selected cell: Hold the [0] key depressed for one second,
the original setting will be returned and the relay will exit the setting mode.
3.4.4 To accept the new setting
Press the [F] key until the confirmation display appears:
Are You Sure?
+ = YES – = NO
1. Press the [0] key if you decide not to make any change.
2. Press the [–] key if you want to further modify the data before entry.
3. Press the [+] to accept the change. This will terminate the setting mode.