VCG202/EN M/H11
 
 
Technical 
 
The remote selection of AUTO and MANUAL modes can only be made when link [SD1] is 
set to ‘1’ or the REMOTE opto-input is energised.  
When switched from a locally selected mode to remote, the relay remains in the last 
locally selected mode until a new mode is selected remotely.  The operating modes of 
AUTO and MANUAL are memorised, so that the relay will revert to the last selected 
mode following an auxiliary power supply interruption. 
Three opto inputs AUTO, MANUAL and REMOTE can be used for local operating mode 
selection.  AUTO and MANUAL select tap change control in service and REMOTE 
enables remote control of AUTO or MANUAL modes.  
In ‘MANUAL’ mode, the tap change initiating signal is independent of the voltage at the 
remote end and does not take line drop compensation or circulating current 
compensation into account.  Also, the delay timer is reset instantaneously and runaway 
protection is disabled as long as MANUAL mode is selected but all other relay functions 
work as normal.  If external switching is used to tap the transformer rather than the relay 
whilst it is in MANUAL mode then the relay will ignore the start position when it is turned 
to AUTO mode thus preventing a runaway alarm. 
In ‘MANUAL’ operating mode, three options are available - Block the tap change, Raise 
voltage or Lower voltage.  After each tap change operation has been signaled the 
selection will automatically return to the idle condition. 
Two output relay masks for ‘Manual Mode’ and ‘Auto Mode’ are provided to allow an 
external indication of the operating mode.   
4.6.1  Remote change of operating mode 
Either link [SD1] must be set to ‘1’ or the REMOTE input mask must be energised before 
the relay will respond to a remote command to change the operating mode. The ‘Mode’ 
command in the STATUS menu is used to remotely or locally select ‘Manual’ or ‘Auto’ 
operating modes.  The operating mode is remembered when the relay is powered down 
and restored on power up.  When link SD1=0 the relay will retain its last set operating 
mode prior to setting SD1=0.  When link [SD1] is set to “0” the operating mode cannot be 
changed via the serial port and the mode command will have no effect on the operating 
mode in use. 
4.6.2   Manual change of operating mode via logic input 
The energisation of the opto input allocated with the input mask ‘MANUAL’ will select the 
‘Manual’ operating mode.  In MANUAL mode, energising either ‘RAISE’ or ‘LOWER’ input 
masks will cause the relay to provide an initiating signal to ‘Raise’ or ‘Lower’ to the tap 
changer. 
4.7  Paralleled transformers 
Primary substation transformers are often operated in parallel in order to improve the 
security of supply.  A common configuration is two transformers positioned adjacently in a 
substation and feeding a common busbar.  Switching is provided to allow the 
transformers to be separated for maintenance purposes but normally the transformers 
operate in parallel.  Sometimes the two transformers are not alike, sometimes more than 
two transformers are paralleled and sometimes transformers several miles apart are 
paralleled. 
In practice it is often required to operate two or more tap changing transformers 
connected in parallel between local busbars.