K
VCG202/EN M/H11
Technical
Manual
KVGC202
3.3.6 Status
Cell Text Status Description
0100 STATUS Column heading
0101 Control READ 1 = Remote ; 2 = Local
0102 Mode SET 1 = Manual ; 2 = Auto
0103 Tap SET No Operation ; Raise V ; Lower V
0104 ST Links
0 = Blocked READ 1 = Tap change operation blocked
1 =V<< blk 1 = Under voltage blocking
2 = V<blkLower 1 = Under voltage detection
3 = V>blkRaise 1 = Over voltage detection
4 = TapFail 1 = Voltage remains outside deadband
5 = Ic>
1 = Excessive circulating current
6 = IL>
1 = Line overcurrent detection
7 = TotalOps> 1 = Tap change operations exceed thresh
8 = FreqOps 1 = Frequent tap change operations
9 = I Rev
1 = Reverse current blocking
A = Run-Away 1 = Invalid tap change operation
B = TapLimit 1 = Tap position above/below threshold
C = IL<
1= Line undercurrent detection
0105 Blocked READ 1 = Tap change operation blocked
0106 V<< blk READ 1 = Under voltage blocking
0107 V<blkLower READ 1 = Under voltage detection
0108 V>blkRaise READ 1 = Over voltage detection
0109 TpFail READ 1 = Voltage remains outside deadband
010A
Ic>
READ 1 = Excessive circulating current
010B
IL>
READ 1 = Line overcurrent detection
010C TotalOps> READ 1 = Tap change operations exceed thresh
010D FreqOps READ 1 = Frequent tap change operations
010E
I rev
READ 1 = Reverse current blocking
010F Run-Away READ 1 = Invalid tap change operation
0110 TapLimit READ 1 = Tap position above/below threshold
0111
IL<
READ 1= Line undercurrent detection
3.3.7 Measure
Cell Text Status Description
0200 MEASURE READ Column heading
0201 Vph-Vph READ Measured line voltage
0202 Vreg READ Regulated voltage = Vbc – Vr – Vx – Vc
0203
Ic
READ Circulating current
0204
IL
READ Load current