VCG202/EN M/H11
 
 
Technical 
 
6.3.2  Alarm indication  
The alarm LED will flash when the password has been entered. It will be lit and remain 
steady when an internal fault has been detected by  its self test routine.  
The alarm flags can then be accessed to determine the fault, provided the relay is still 
able to perform this function.  See chapter 3, Chapters 3.3.5 and 3.6 for more information 
on alarm the flags. 
6.3.3  Blocked indication 
When the tap change operation is blocked (RaiseV and LowerV), it is indicated by a 
CONTROL LED and a relay output contact (BLOCKED) allocated in the relay mask. The 
tap change operation can be blocked for any of the following conditions: 
-  Tap change failure [Tfail) 
-  Number of tap change operations [TotalOps] 
-  Frequent tap change operations [FreqOps] 
-  Run Away protection [RunAway] 
-  Block logic input mask (0706) is manually initiated 
The CONTROL LED will be flashing for any of the above conditions except for manual 
blocking, for which it will illuminate continually. It is also lit permanently during tapping if 
the inter tap delay time is set to zero for continuous tap change operation.   
6.4  Functional alarms 
A relay output should be allocated in the relay mask to give an alarm condition for any of 
the functions described in this Chapter.  The relay masks can be found in chapter 3, 
Chapter 3.3.12. of this service manual.  The logic diagram showing the logic for each of 
the functions can be found in Appendix 2. 
6.4.1  Raise/lower volts indication 
Relay outputs can be allocated in the relay masks to give an indication for raise and lower 
volts tap change.  
6.4.2  Blocked indication 
Relay output can be allocated in the relay masks to give an indication for the blocked 
condition. 
6.4.3  Undervoltage blocking (V<<) 
If the system voltage falls below the undervoltage blocking setting value, the 
undervoltage detector will operate and instantaneously reset the initial time delay thus 
inhibiting the relay outputs to ‘Raise’ or ‘Lower’ tap change operations.  
V<< output relay allocated in the relay mask will pick up the undervoltage blocking 
condition to give the alarm indication. 
The pick-up/drop-off ratios on the undervoltage blocking detection is +5% of the threshold 
setting.  
6.4.4  Undervoltage detection (V<) 
The undervoltage detector block operations that would  lower the voltage further thus 
defining the minimum working limit of the transformer and allowing tap changes in such a 
direction as to restore the regulated voltage. 
V< output relay allocated in the relay mask will pick up the undervoltage detection 
condition to give the alarm indication.  
The pick-up/drop-off differentials on the undervoltage detectors is +1% of the threshold 
setting.