Manual
 
 
KVCG202/EN M/H
 
 
7.5  Setting control 
Control functions via a KVGC202 relay can be performed over the serial communication 
link.  They include change of relay settings, change of setting groups, remote control of 
the operating modes.  
Remote control is restricted to those functions that have been selected in the relays menu 
table and the selection cannot be changed without entering the password.  
CRC and message length checks are used on each message received.  No response is 
given for received messages with a detected error.  The Master Station can be set to 
resend a command a set number of times if it does not receive a reply or receives a reply 
with a detected error. 
Note:  Control commands are generally performed by changing the value 
of a cell and are actioned by the setting change procedure, as 
described in Chapter 7.3.1, and have the same inherent security.  
No replies are permitted for global commands as this would cause 
contention on the bus; instead a  double send is used for 
verification of the message by the relay for this type of command.  
Confirmation that a control command, or setting change, has been 
accepted is issued by the relay and an error message is returned 
when it is rejected.  
  The command to change setting group does not give an error 
message when the group 2 settings are disabled unless link 
SD3=0 to inhibit response to a remote setting group change 
commands.  
7.5.1  Remote setting change 
The relay will only respond to setting change commands via the serial port if link SD1=1.  
Setting SD1=0 inhibits all remote setting changes with the exception of the SD software 
links and the password entry.  Thus, with link SD1=0, remote setting changes are 
password protected.  
To change them, the password must be remotely entered and the function link SD 
function link SD1 set to “1” to enable remote setting changes.  When all setting changes 
have been made set link SD1=0 to restore password protection to remote setting 
changes.  
7.5.2  Remote control of setting group 
The setting group selection is fully described in chapter 5, Chapter 5.2 including the 
remote control of this function.  Group 2 must be activated before it can be selected by 
setting software link SD4=1.  Set link SD3=1 to enable the relay to respond change 
setting group commands, via the serial port to select group 2 and set SD4=1 to inhibit this 
function.  
If the remote setting changes have been selected to have password protection, as 
described in Chapter 7.5.1, then it can also be applied to the remote setting group 
selection as follows. Set link SD3=0 to inhibit remote setting changes, then set link 
SD1=1 to enable remote setting changes and set link CTL2=1.  The group 2 settings will 
then be in operation and setting link SD1=0 will restore the password protection. 
If conventional SCADA has an output relay assigned to select the alternative setting 
group then it may be used to energise a logic input assigned in the input mask [070A 
STG GRP 2].  In this case set link SD3=0. 
7.6  Loadshedding/boosting control 
7.6.1  Remote control of loadshedding/boosting 
The KVGC202 relay responds to the loadshedding/boosting by level Courier commands.  
These commands are used to control the level of loadshedding/boosting of the KVGC202 
relay.  The relay retains the selected level until new command is received or an opto input 
is energised, which overrides the command over the serial port. The settings are stored 
by the relay when the relay is powered-down and restored again on power-up.