Technical
Manual
KVCG202/EN M/H
11
KVGC202
Cell Text Status Description
0815 Select tst rlys PWP Select relays to operate when relay test is selected
0816 Test Relays = [0] PWP Press [0] key to close relays selected
3.4 Changing text and settings
Settings and text in certain cells of the menu can be changed via the user interface. To
do this the cover must be removed from the front of the relay so that the [+] and [] keys
can be accessed.
3.4.1 Quick guide to menu controls
Quick Guide to Menu Control with the Four Keys
Current display Key press Effect of action
Default display [0] long
[0] short
[F]
[+]
[–]
Back-light turns ON Reset condition monitor
Select current display as default
Steps through the available default displays
Steps down to column heading SYSTEM
DATA.
Back-light turns ON Reset condition monitor
Back-light turns ON Select current display as
default
Column heading [0]short
[0]long
[F]long
[F]short
[–]
[+]
Back-light turns ON - no other effect.
Re-establishes password protection immediately
and returns the default display.
Move to next column heading
Steps down the menu to the first item in the
column.
Move to next column heading
Move to previous column heading
Any menu cell [F]short
[F]long
[F]+[0]long
[0]short
[0]long
Steps down the menu to the next item in the
column.
Displays the heading for the next column.
Steps back up the menu to the previous item.
Back-light turns ON no other effect.
Resets the value if the cell is resettable.
Any settable cell [+] or [–] Puts the relay in setting mode. The password
must first be entered for protected cells.
Setting mode [0]
[+]
[–]
[F]
Escapes from the setting mode without a setting
change.
Increments value with increasing rapidity if held.
Decrements value with increasing rapidity if
held.
Changes to the confirmation display.
If function links, text, relay or input masks are
displayed the [F] key will step through them from
left to right and finally change to the confirmation
display.
Confirmation mode [+]
[–]
[0]
Confirms setting and enters new setting or text.
Returns prospective change to check/modify.
Escapes from the setting mode without change.
The actions shown in italic text can only be performed when the cover is removed.