5.3.4  Initial logic settings 
Logic  Symbol  Factory Settings 
Undervoltage total inhibit level (% of Vs)  V<<  80V 
Undervoltage blocking limit  V<  100V 
Overvoltage blocking limit  V>  120V 
Over/under voltage blocking timer  tV<V>  0s 
Total time outside dead band to = failure  tFAIL  180s 
Excessive circulating current threshold 
Ic> 
0.05A (1A) 
0.25A (5A)     
Excessive circulating current time delay 
t
IC 
0s 
Line overcurrent threshold 
IL> 
1.2A (1A) 
6.0A (5A) 
Line under current threshold 
IL< 
0A (1A or 5A) 
Total number of taps available  TpAvail  20 
Upper tap alarm limit  TP>  16 
Lower tap alarm limit  TP<  4 
Total number of tap change operations  total ops>  5000 
Number of tap changes allowed in time tP  opstP>  40 
Time period  tP  24 
Relay test hold timer  tTest relay  1s 
5.3.5  Preferred use of logic inputs  
The following is not mandatory, but it is suggested that it is followed where possible so 
that different schemes will use the particular logic input for the same, or similar function. 
INPUT MASKS  DEFAULT SETTINGS 
Remote  00000000 
Automatic  00000001 
Manual  00000010 
Raise V  00000100 
Lower V  00001000 
Block  00010000 
Level 1  00100000 
Level 2  01000000 
Level 3  10000000 
Stg Grp2  00000000 
5.3.6  Preferred use of output relays 
The following is not mandatory, but it is suggested that it is followed where possible so 
that different schemes will use a particular output relay for the same or similar function.  
RELAY MASKS  DEFAULT SETTINGS 
Raise V  00000001 
Lower V  00000010 
Blocked  00000100 
UnBlocked  00001000 
V<<  00010000