3.3.12 Input masks
Cell Text Status Description
0700 INPUT MASKS READ Column heading
0701 Remote PWP Logic input for remote selection of Auto/Manual mode
0702 Automatic PWP Logic input to select automatic mode
0703 Manual PWP Logic input to select manual mode
0704 Raise V PWP Logic input to manually initiate signal to raise the tap
changer
0705 Lower V PWP Logic input to manually initiate signal to lower the tap
changer
0706 Block PWP Logic input to block tap change operation (raise and
lower)
0707 Level 1 PWP Logic input for load shedding/boosting level 1
0708 Level 2 PWP Logic input for load shedding/boosting level 2
0709 Level 3 PWP Logic input load shedding/boosting level 3
070A Stg Grp2 PWP Logic input to select group 2 settings from external
input
3.3.13 Relay masks
Cell Text Status Description
0800 RELAY MASKS READ Column heading
0801 Raise V PWP Indication for raise volts tap change block
0802 Lower V PWP Indication for lower voltage tap change block
0803 Blocked PWP Indication if both raise and lower tap change
operations are inhibited
0804 UnBlocked PWP Indication if tap change operations are not inhibited
0805 V<< PWP Alarm indication for under voltage blocking
0806 V< PWP Alarm indication for under voltage detection
0807 V> PWP Alarm indication for over voltage detection
0808 Tap Fail PWP Alarm indication for tap changer failure
0809
Ic>
PWP Alarm indication for excessive circulating current
detector
080A
IL>
PWP Alarm indication for overcurrent detector
080B
IL<
PWP Alarm indication for undercurrent detector
080C TotalOps> PWP Alarm indication for tap change operations exceed a
preset value
080D FreqOps PWP Alarm indication for tap change operations exceed
threshold over preset time period
080E
I rev
PWP Alarm indication for reverse current condition
080F RUN-AWAY PWP Alarm indication for invalid tap change operation
0810 Tap Limit PWP Alarm indication for tap position indicator outside the
set threshold settings
0811 Tap Odd PWP Current tap position is odd
0812 Tap Even PWP Current tap position is even
0813 Auto Mode PWP Relay is in ‘Automatic’ mode
0814 Manual Mode PWP Relay is in ‘Manual’ mode