K
VCG202/EN M/H11
Technical
Manual
KVGC202
8.9.3 Directional
Operating boundary 0 180° accuracy ±3°
PU DO differential less than 3° (typically <1°)
8.9.4 Measurements
Measured voltage ±2% Vn (typical)
±0.3% Vn over the range 70 160V (typical)
Load current
±2%
In (typical)
Circulating current
±5%
In (typical)
±10% In at <100mA
Power factor ±5%
Frequency
(45 65Hz)
±1% (typical)
8.10 Influencing quantities
8.10.1 Ambient temperature
Operative range 25 to +55°C
Current settings ±1%
Voltage settings ±0.03% per °C
Operation times ±1%
Angle measurement <2°
8.10.2 Frequency
With frequency tracking
Operative range 46 to 65Hz
Current setting ±1%
Voltage settings ±1%
Operating times ±1%
Angle measurement <1°
Without frequency tracking
Reference range 47Hz to 51Hz or 57Hz to 61Hz
Operating times ±2%
8.10.3 Angle measurement <2°
Auxiliary supply Nominal Operative range
24/125V 19 to 150V dc
50 to 133V ac
48/250V 33 to 300V dc
87 to 265V ac
Current settings ±0.5%
Voltage settings ±0.5%
Operation times ±0.5%
Angle measurement ±0.5°