Cell Text Status Description
050C tINTER SET Inter tap delay
050D tPULSE SET Tap pulse duration
050E Level 1 SET Load shedding/boosting level 1
050F Level 2 SET Load shedding/boosting level 2
0510 Level 3 SET Load shedding/boosting level 3
0511 tTapChange SET Time between tap position indications
3.3.11 Logic 2
Cell Text Status Description
0600 LOGIC 2 READ Column heading
0601 LOG Links PWP Software links that are used to select the available
optional group 2 blocking functions
1 TpFail 1 = block outside dead band for maximum time
2 Ic> blk 1 = block for excessive circulating current
3 IL> blk 1 = block for excessive load current
4 Total opsBlk 1 = block for excessive number of operations
5 Freq opsBlk 1 = block for frequent operation
6 Irev BLK 1 = block operation for reverse current flow
7 Runaway blk 1 = block for tap change runaway
8 IL<BLK 1= block for insufficient current
0602 V<< SET Under voltage total inhibit level (% of Vs)
0603 V< SET Over voltage blocking limit
0604 V> SET Under voltage blocking limit
0605 t V< V> SET Under/over voltage blocking timer
0606 tFAIL> SET Total time outside dead band to = failure
0607
Ic>
SET Excessive circulating current threshold
0608
t
IC
SET Excessive circulating current time delay
0609
IL>
SET Line overcurrent threshold
060A
IL<
SET Line undercurrent threshold
060B TpAvail SET Total number of taps available
060C TP> SET Upper tap alarm limit
060D TP< SET Lower tap alarm limit
060E total ops> SET total number of tap change operations
060F ops/tP> SET Number of tap changes allowed in time tP
0610 tP SET Time period tP
0611 Default Display SET Default display required (Multi Data / Time Remain /
Vreg TapPos / IL IC / Operating Mode / Plant Ref /
Description / Manufacturer)
0612 tTest Relay SET Relay test hold timer