Technical
Manual
KVCG202/EN M/H
11
KVGC202
5. RELAY SETTINGS
5.1 Relay settings
All the settings can be entered into the relay via the front keypad or using a PC with a K-
Bus connection. The selection can be made in the menu columns for settings, but
password might be required before some settings can be entered. Two setting groups
are available to allow the user to set Group 1 to normal operating conditions while Group
2 can be set to cover abnormal operating conditions.
The quantities that require setting are listed below with the adjustment range and step
sizes:
Setting Symbols KVGC adjustment range In steps of
Setting voltage Vs 90 139V 0.1V
Dead band dVs ±0.5% to ±20% of Vs 0.1%
Circulating current
Ic 0.02 0.5A (In = 1A)
0.1 2.5A (
In = 5A)
0.01A
0.05A
Load current
IL> 0.5 2A (In = 1A)
2.5 10A (In = 5A)
0.05A
Load current
IL< 0 1A (In = 1A)
0 5A (
In = 5A)
0.10A
Circulating current
compensation
Vc 0 50V 1.0V
Resistive line drop
compensation
Vr 0 50V 1.0V
Reactive line drop
compensation
Vxl 0 50V 1.0V
Reverse reactance
control
Internal reversal of V
XL
vector
Initial delay (tINIT): Definite
Inverse
0 20 secs
20 300 secs
See Chapter 6.3.3
1 sec
10 secs
Intertap delay tINTER 0 120 secs 0.1 secs
Tap pulse duration tPULSE 0.5 5 secs 0.5 secs
Load (3 Steps)
shedding/boosting
0 ±10% of Vs 1%
Under voltage detection V< 80 130V 1.0V
Over voltage detection V> 105 160V 1.0V
Under voltage blocking V<< 60 130V 1.0V
Total taps available TapsAvail 1 30 Ext volt/140 VT 1
Maximum tap position TP> 1 30 Ext volt/140 VT 1
Minimum tap position TP< 1 30 Ext volt/140 VT 1
Total no. of tap changes TotalOps> 1 10000 1
Tap changer operations Ops/tP> 1 100 1
Time period tP 1 24 hrs 1 hr
Excessive circulating
current time delay
tIC
0 180 secs 10 secs
Alarm initiation time delay tFAIL> 0 15 mins 30 secs
Power factor angle setting PF Angle 0 90 degrees 1 degree
tV<V> tV<V> 0 300 secs 5 secs