EasyManua.ls Logo

GE KVGC 202 - Opto-Isolated Inputs

GE KVGC 202
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical
Manual
KVCG202/EN M/H
11
KVGC202
8.11 Opto-isolated inputs
Capture time 12.5 ±2.5ms at 50Hz
10.4 ±2.1ms at 60Hz
Release time 12.5 ±2.5ms at 50Hz
10.4 ±2.1ms at 60Hz
Minimum operating voltage >35V dc
Maximum operating voltage 50Vdc
Input resistance
10k (add 12k for every additional 50V
inexcess of 50V)
Maximum series lead resistance
2k for single input at 40V min.
1k for 2 inputs in parallel at 40V min
0.5k for 4 inputs in parallel at 40V min
Maximum ac induced loop voltage 50V rms (thermal limit)
Maximum capacitance coupled
ac voltage
250V rms via 0.1µF
8.12 Output relays
Output relays 0 to 7
Type 1 make
Rating Make 30A and carry for 0.2s
Carry 5A continuous
Break DC 50W resistive
25W inductive (L/R = 0.04s)
AC 1250VA (maxima of 5A)
Subject to a maxima of 5A and 300V
Watchdog
Type 1 make + 1 break
Rating Make 10A and carry for 0.2s
Carry 5A continuous
Break DC 30W resistive
DC 15W inductive (L/R = 0.04s)
AC 1250VA (maxima of 5A)
Subject to a maxima of 5A and 300V
Durability >10,000 operations
8.13 Operation indicator
3 Light Emitting Diodes - internally powered.
16 character by 2 line Liquid Crystal Display (with backlight).
8.14 Communication port
Language Courier
Transmission Synchronous RS485 voltage levels
Format HDLC
Baud Rate 64k/bit per second
K-Bus Cable Screened twisted pair
Length 1000m
Bus Loading 32 units (mulitdrop system)

Table of Contents