Manual
 
 
KVCG202/EN M/H
 
 
 
Figure 24:  Parallel connection of LDC circuits 
The following notes demonstrate how the LDC CTs may be paralleled on a KVGC202 
relay. 
2RL1  =  Lead loop resistance between CT1 and AVR1 plus resistance of AVR  
    circulating current CT input, KVGC202 terminals 23 and 24 for In=1A  
    or terminals 25 and 26 for In=5A. 
XM1  =  CT1 magnetising impedance which will be ignored due to its high value  
    when CT is unsaturated. 
RCT1 =  CT1 winding resistance. 
RL  =  Resistance of one lead between AVRs (including any interposing CTs). 
CT1  =  Driving CT (T1 loaded). 
CT2  =  Idling CT (T2 loaded). 
2IL  =  Current flowing in line(s) fed by T1/T2 which creates line voltage drop,  
    which is to be compensated for.