Chapter 3: Configuration
GFK-2958E RSTi-EP User Manual 41
Ch 0: Counter behavior internal
gate
Interrupt counting (0)
/ Cancel counting (1)
interrupt counting
Ch 0: End value
-2147483648 ...
2147483647
2147483647
Ch 0: Load value
-2147483648 ...
2147483647
0
Ch 0: Hysteresis
0 ... 255
0
Ch 0: Pulse duration
0 ... 255 [Input value x
2 = output time;
corresponds to
0 ... 510 ms]
0
Product
Part No.
Parameter
Optional values
Default value
2 Channel High
Speed Counter, AB
100 kHz
EP-5112
Diagnostic alarm
disabled (0) /
enabled (1)
disabled
Ch 0 ... Ch 1: Filter time signal A
0,01 ms [100 kHz] (0)
/ 0,017 ms [50 kHz]
(1) / 0,033 ms [30
kHz] (2) / 0,1 ms [10
kHz] (3) / 0,2 ms [5
kHz] (4) / 0,5 ms [2
kHz] (5) / 1 ms [1 kHz]
(6)
0,01 ms
Ch 0 ... Ch 1: Filter time signal B
0,01 ms [100 kHz] (0)
/ 0,017 ms [50 kHz]
(1) / 0,033 ms [30
kHz] (2) / 0,1 ms [10
kHz] (3) / 0,2 ms [5
kHz] (4) / 0,5 ms [2
kHz] (5) / 1 ms [1 kHz]
(6)
0,01 ms
Ch 0 ... Ch 1: Process alarm
overflow
disabled (0) /
enabled (1)
disabled
Ch 0 ... Ch 1: Process alarm
underflow
disabled (0) /
enabled (1)
disabled
Ch 0 ... Ch 1: Process alarm
comp. value
disabled (0) /
enabled (1)
disabled
Ch 0 ... Ch 1: Process alarm end
value
disabled (0) /
enabled (1)
disabled
Ch 0 ... Ch 1: Counting mode
count endless (0) /
once - forward (1) /
once - backwards (2)
/ once - no main
direction (3) /
periodic - forward (4)
/periodic -
backwards
(5)/periodic no main
direction (6)
count endless

Table of Contents