VLT
®
5000 Series
■ General technical data
■ General technical data
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ...................................................................... 3 x 200/208/220/230/240V ±10%
Supply voltage 380-500 V units ............................................................... 3 x 380/400/415/440/460/500V ±10%
Supply frequency ........................................................................................................................ 48/62 Hz +/- 1%
Max. imbalance of supply voltage: .......................................................................................................................
VLT 5001 - 5011 / 380 - 500 V and VLT 5001 - 5006 / 200 - 240 V ................... ±2.0% of rated supply voltage
VLT 5016 - 5062 / 380 - 500 V and VLT 5008 - 5027 / 200 - 240 V ................... ±1.5% of rated supply voltage
VLT 5060 - 5500 / 380 - 500 V and VLT 5032 - 5052 / 200 - 240 V ................... ±3.0% of rated supply voltage
True Power factor (
) ................................................................................................... 0.90 nominal at rated load
Displacement Power Factor (cos
'
) ......................................................................................... near unity (>0.98)
No. of switches on supply input L1, L2, L3 .......................................................................... approx. 1 time/min.
Max. shortcircuit rating ......................................................................................................................... 100,000 A
See the section on special conditions in the Design Guide
VLT output data (U, V, W):
Output voltage .............................................................................................................. 0-100% of supply voltage
Output frequency ............................................................................................................ 0 - 132 Hz, 0 - 1000 Hz
Rated motor voltage, 200-240 V units ............................................................................. 200/208/220/230/240V
Rated motor voltage, 380-500 V units ............................................................... 380/400/415/440/460/480/500V
Rated motor frequency ........................................................................................................................... 50/60 Hz
Switching on output ................................................................................................................................ Unlimited
Ramp times ................................................................................................................................... 0.05-3600 sec.
Torque characteristics:
Starting torque, VLT 5001-5027, 200 - 240 V and VLT 5001-5062, 380 - 500 V ....................... 160% for 1 min.
Starting torque, VLT 5032 - 5052, 200 - 240 V and VLT 5060-5500, 380 - 500 V .................... 150% for 1 min.
Starting torque .......................................................................................................................... 180% for 0.5 sec.
Acceleration torque ...................................................................................................................................... 100%
Overload torque, VLT 5001-5027, 200 - 240 V and VLT 5001 - 5062, 380 - 500 V ................................... 160%
Overload torque, VLT 5032 - 5052, 200 - 240 V and VLT 5060-5500, 380 - 500 V ................................... 150%
Arresting torque at 0 rpm (closed loop) ....................................................................................................... 100%
The torque characteristics given are for the VLT frequency converter at the high overload torque level (160%).
At the normal overload torque (110%), the values are lower.
Control card, digital inputs:
Number of programmable digital inputs .............................................................................................................. 8
Terminal nos. .......................................................................................................... 16, 17, 18, 19, 27, 29, 32, 33
Voltage level ....................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ .......................................................................................................................... < 5 V DC
Voltage level, logical ’1’ ......................................................................................................................... >10 V DC
Maximum voltage on input ...................................................................................................................... 28 V DC
Input resistance, R
i
........................................................................................................................................ 2 k
Scanning time per input ............................................................................................................................ 3 msec.
MG.51.A1.02 - VLT is a registered Danfoss trade mark
8