EasyManua.ls Logo

GEA ARIETE - Stator Reactance; Motor Magnetizing, 0 Rpm; Min. Frequency Normal Magnetizing

GEA ARIETE
556 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VLT
®
5000 Series
3. The values are obtained by means of manual
measurements:
-R
S
can be calculated by measuring the resis-
tance R
PHASE-to-PHASE
between two phase
terminals. If R
PHASE-to-PHASE
is lower than 1-2
ohm (typically motors >4-5.5 kW, 400 V), a spe-
cial ohm-meter should be used (Thomson bridge
or similar). R
S
= 0.5 x R
PHASE-to-PHASE
4. The factory settings of R
S
, selected by the VLT
frequency converter itself on the basis of the mo-
tor nameplate data, are used.
NB!:
If the setting in parameter 102-109 is
changed, the parameters 110-118 will return
to factory setting.
109
109 Stator reactance
(STATOR REACT.)
Value:
depends on the choice of motor
Function:
After setting motor data in parameters 102-106, a
number of adjustments of various parameters are
made automatically, including the stator resistance
X
S
. The shaft performance can be improved by ne-
tuning R
S
and X
S
, see procedure below.
Description of choice:
X
S
can be set as follows:
1. Automatic motor adaptation, where the VLT fre-
quency converter measures on the motor to
determine the value. All compensations are reset
to 100%.
2. The values are stated by the motor supplier.
3. These values are obtained by means of manual
measurements:
-X
S
can be calculated by connecting a motor to
mains and measuring the phase-to-phase voltage
U
L
as well as the idling current I .
Alternatively , these values can be recorded dur-
ing operation in idle running state at the rated
motor frequency f
M,N
, slip compensation (par.
115) = 0% and load compensation at high speed
(par. 114) = 100%.
X
S
=
U
L
p
3
xl
8
4. The factory settings of X
S
, selected by the VLT
frequency converter itself on the basis of the mo-
tor nameplate data, are used.
NB!:
If the setting in parameter 102-109 is
changed, the parameters 110-118 will return
to factory setting.
110
110 Motor magnetizing, 0 rpm
(MOT. MAGNETIZING)
Value:
0 - 300 %
100 %
Function:
This parameter can be used if a different thermal
load on the motor is desired when running at low
speed.
This parameter is used in connection with parameter
111.
Description of choice:
Enter a value stated as a percentage of the rated
magnetizing current.
Too low setting may lead to a reduced torque on the
motor shaft.
111
111 Min. frequency normal magnetizing
(MIN FR NORM MAGN)
Value:
0.1 - 10.0 Hz
1.0 Hz
Function:
This parameter is used in connection with parameter
110. See drawing in parameter 110.
Description of choice:
Set the required frequency (for normal magnetizing
current). If the frequency is set lower than the motor
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A1.02 - VLT is a registered Danfoss trade mark
114

Table of Contents

Related product manuals