VLT
®
5000 Series
Application conguration
Using this parameter enables the choice of a cong-
uration (setting) of the VLT frequency converter that
ts the application in which the VLT frequency con-
verter is to be active.
NB!:
First, the motor nameplate
date must be set in parameters 102-106.
There is a choice of the following congurations:
- Speed control, open loop
- Speed control, closed loop
- Process control, closed loop
- Torque control, open loop
- Torque control, speed feedback
The selection of special motor characteristics can be
combined with any application conguration.
Setting of parameters
Select Speed control, open loop if a normal speed
adjustment without external feedback signals is re-
quired (the internal slip compensation is operating)
from motor or unit.
Set the following parameters in order shown:
Speed control, open loop:
Parame-
ter:
Setting: Data value:
100 Conguration Speed control, open loop [0]
200 Output frequency range/direction
201 Output frequency low limit Only if [0] or [2] in par. 200
202 Output frequency high limit
203 Reference/feedback range
204 Minimum reference Only if [0] in par. 203
205 Maximum reference
Select Speed control, closed loop if the application
has a feedback signal and the accuracy in Speed
control, open loop is not sufcient or a full holding
torque is required.
Set the following parameters in order shown:
Speed control, closed loop (PID):
Parame-
ter:
Setting: Data value:
100 Conguration Speed control, closed loop [1]
200 Output frequency range/direction Output frequency low limit
201 Output frequency low limit
202 Output frequency high limit
203 Reference/feedback range
414 Minimum feedback Only if [0] or [2] in par. 200
415 Maximum feedback
204 Minimum reference Only if [0] in par. 203
205 Maximum reference
417 Speed PID proportional gain
418 Speed PID integration time
419 Speed PID differentiation time
420 Speed PID diff. gain limit
421 Speed PID lowpass lter time
MG.51.A1.02 - VLT is a registered Danfoss trade mark