VLT
®
5000 Series
Description of choice:
Set the value to the desired maximum value of the
current signal output.
Maximum value:
The output can be scaled to give a lower current
than 20 mA at full scale or 20 mA at an output below
100% of the maximum signal value.
If 20 mA is the desired output current at a value be-
tween 0 - 100% of the full-scale output, program the
percentage value in the parameter, i.e. 50% = 20
mA.
If a current between 4 and 20 mA is desired at maxi-
mum output (100%), the percentage value to
program in the drive is calculated as:
0
mA=desired maximum c urrent
3
100%
,
i.e.
0
mA
=
20
10
3
100 = 200%
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A1.02 - VLT is a registered Danfoss trade mark
142