Signal Exchange with Machine Control Automatic operation
EN 3925-0060 V207-00 MANUAL R03.doc
HeMaTech
Prüftechnik
Automatic operation
The signal Automatic must be applied, followed by the signal Machine ready, the out-
put signal ready for test is set and the selected Program number is read in. The signals
Ready for operation and test result are reset at the same time. Now the measurement
can be triggered with the signal Start (pulse of approx. 1 second). Remove the signal
Machine ready.
Once the measurement is finished, the test result (no leak, Leak or rework) is submitted
and the output ready for operation is set.
NOTE!
The signal machine ready must be set before each measurement,
whereby the signal for program selection may always be present.