160 MPA2C3 User Manual
1. Open the panel’s cabinet
2. Power OFF the panel.
a. Note the current address of the panel reading DIP Switch positions of SW1
bit 5, 6, 7, 8 and 9 (Address 5, Address 4, Address 3, Address 2 and Address
1). (You need this in step 4a. again)
b. Set DIP Switch positions of SW1 bit 3, 5, 6, 7, 8 and 9 (Primary, Address 5,
Address 4, Address 3, Address 2 and Address 1) to ON position. Make DIP
switch 3,5,6,7,8, and 9 ON.
3. Power ON the panel.
a. Connect to the panel with a computer or laptop via Ethernet ETH1 (HOST)
or USB2 (WEB MODE).
b. Log in to web login with reset default administrator username and
password.
i. Follow instructions to create a new administrator password in the Web
interface
c. Log off
4. Power OFF the panel
a. Set DIP Switch positions of SW1 bit 5, 6, 7, 8 and 9 (Address 5, Address 4,
Address 3, Address 2 and Address 1) to the original positions noted in step
2a.
5. Power ON the panel
6. Close the panel’s cabinet
7. From here use the new administrator password to login the web interface
Note: Password reset is enabled only for admin account.
Note: The password reset only resets the password, however the configuration of the panel
will not be reset to factory default.