70 MPA2C3 User Manual
8. Click Save.
Configuring Output Groups
Note: You must select at least one output before you can create a group.
The Output Groups tab allows you to configure the following:
• A group of horns to sound for a set time during a set period
• Energize or de-energize a group of doors during a set period
In the Output Groups tab, you can configure the following for one or more groups:
• Pulse time
• Disable/Enable Latch
• Energized (schedule selection)
• Disable Interlock (schedule selection)
Pulse Time Configure how long a device assumes abnormal status, such
as a horn sounding or a released door strike. In hours:min-
utes:seconds. Maximum time is 1:45:59.
Latch Toggles the state of the outputs between energized and de-
energized status upon every activation (code use, interlock, or
manual pulse).
Interlocks Disable/enable interlocks. See
Configuring Interlocks on page 53 for
more about Interlocks.
Energized Specifies the period during which the output relay is automat-
ically energized. Select a schedule (that you created in
Entering a
Panel Name
section on page 42) from the drop-down list.
Disable Interlocks Specifies the period during which the interlocks that control
the output will be disabled. Select a schedule (that you cre-
ated in
Entering a Panel Name section on page 42) from the drop-
down list.
Table 2-11
Setting Description