80 MPA2C3 User Manual
Deleting Interlocks
1. Click to select an Interlock.
Figure 2-37 Deleting an Interlock
2. Click the Delete button . A message appears asking for confirmation.
3. Click OK.
Enabling/Disabling Interlocks
• Click the Enable/Disable button . A confirmation appears if successful.
Downstream Devices
The NETAXS® I/O devices provide the MPA2C3 panels with additional inputs and
outputs. The MPA2C3 panels supports two Interface types:
• NX4IN - Provides 32 supervised, four-state inputs that are limited to 2.2K ohms
resistance. The NX4IN must be assigned network addresses 1 and 2.
• NX4OUT - Provides 2 supervised inputs and 16 SPDT relay outputs; each input
is limited to 2.2K ohms resistance. The NX4OUT must be assigned network
addresses 3-6.
Note: The NX4IN and NX4OUT network addresses are set by the DIP switches on each
board. Refer to the NETAXS® NX4IN/NX4OUT Input/Output Configuration Guide for
more information about configuring the NX4IN and NX4OUT boards.
Note: MPA2C3 panel supports a maximum of six daisy-chained Interface boards - two
NX4IN and four NX4OUT boards. The boards connect to the MPA2C3 panel's RS-485
Interface Bus (J16).