MPA2C3 User Manual 71
1. Navigate to the Output Groups tab: Click Panel Configuration
> Outputs >
Groups.
Figure 2-33 Configuring Output Groups
2. Click to add a new group.
3. Configure the following for each output group:
4. Click toggle(s) to select outputs. Click the Choose Outputs toggle to select all
outputs.
5. Click Save.
Table 2-12
Setting Description
Name Enter a unique name for the group
Pulse Time Configure how long a device assumes abnormal status, such as a
horn sounding or a released door strike. In
hours:minutes:seconds. Maximum time is 1:45:59.
Latch Toggles the state of the outputs between energized and de-
energized status upon every activation (code use, interlock, or
manual pulse).
Energized Specifies the period during which the group of output relays are
automatically energized. Select a schedule (that you created in
Entering a Panel Name section on page 42) from the drop-down
list.
Disable Interlocks Specifies the period during which the interlocks that control the
group’s outputs will be disabled. Select a schedule (that you
created in
Entering a Panel Name section on page 42) from the
drop-down list.