Table 8–23: Contact ID Event Definition Codes (continued)
EVENT DATA TYPE
158 High temp Zone
159 Low temp Zone
161 Loss of air flow Zone
162 Carbon Monoxide detected Zone
163 Tank level Zone
SUPERVISORY
Fire Supervisory -200 and 210
200 Fire Supervisory Zone
201 Low water pressure Zone
202 Low CO2 Zone
203 Gate valve sensor Zone
204 Low water level Zone
205 Pump activated Zone
206 Pump failure Zone
TROUBLES
System Troubles -300 and 310
300 System Trouble Zone
301 AC Loss Zone
302 Low system battery Zone
303 RAM Checksum bad Zone
304 ROM checksum bad Zone
305 System reset Zone
306 Panel programming changed Zone
307 Self-test failure Zone
308 System shutdown Zone
309 Battery test failure Zone
310 Ground fault Zone
311 Battery Missing/Dead Zone
312 Power Supply Over current Zone
313 Engineer Reset User
314 Primary Power Supply Failure Zone
Sounder / Relay Troubles -320
320 Sounder/Relay Zone
321 Bell 1 Zone
322 Bell 2 Zone
323 Alarm relay Zone
324 Trouble relay Zone
325 Reversing relay Zone
326 Notification Appliance Ckt. # 3 Zone
327 Notification Appliance Ckt. #4 Zone
System Peripheral Trouble -330 and 340
330 System Peripheral trouble Zone
331 Polling loop open Zone
332 Polling loop short Zone
333 Expansion module failure Zone
334 Repeater failure Zone
335 Local printer out of paper Zone
336 Local printer failure Zone
337 Exp. Module DC Loss Zone
338 Exp. Module Low Batt. Zone
339 Exp. Module Reset Zone
341 Exp. Module Tamper Zone
342 Exp. Module AC Loss Zone
343 Exp. Module self-test fail Zone
344 RF Receiver Jam Detect Zone