5–14
Table 55: Communications Options and Description (contd)
Communications
Menu
Choices Options Default Comments
Ack Timeout
1-120 seconds 4 sec 15 seconds or less in UL applications. See Section
5.4.3.5 for programming steps.
<Cfg>
Term=013
Head=010
Ack=006
Nack=021
Time
Req=005
Time
Head=084
Time
Term=020
Only visible if ADEMCO 685, FBII220 or CAPS ONLY
format is selected.
Note: Setting Ack and Nack to 0 disables Ack and
Nack.
Y = Enabled
Sep
N = Disabled
Only visible if SK9000 format is selected. When
enabled, a hex 05 is output for an account separator.
When not selected, a hex 2E is output for an account
separator.
Log
Records
Y = Enabled Enable
External
ID
N = Disabled
Super
Char
s
No Data
Char
0
6.1
Automation Cfg
(continued)
<ITI>
Generic
Revision
6.2
Only visible if ITI Gen or ITIComp format is selected.
Yes
Printer
No
Yes
Bkp Printer
No
Yes
Auto Comp
No
Yes
Bkp Auto Comp
No
Yes = will annunciate on the receiver sounder if an
event, trouble or fault condition occurs.
No = no annunciation if an event, trouble or fault
condition occurs.
See Section 5.4.3.6 for programming steps.
Yes
Battery
No
Yes
Device
No
Device corresponds to loss of communication with slave
or line card.
Yes
Line Fault
No
Yes
AC Power
No
Yes
Buffer Full
No
Yes
Listen In
No
Listen in must be set to No for UL installations.