Section 5 – Programming
5–37
Table 511: Line Device Menu Options (contd)
Select
Device
Type
Line
Device
Menu
Choice Choice Choice Choice Default Comments
Misc. Line
Options
(contd)
Call Hang-
up
60-180 sec 120 sec
Sets the maximum
amount of time that a
call can last before the
receiver hangs up on
the call if an event is
not in progress. See
page 566 for details.
4/2
BFSK Auto
High Speed
In High Speed,
messages with event
codes of B, C, E, and
F are translated to
ADEMCO High Speed
messages.
3/1
3/1 Restore
High Speed
Standard method:
123 2, 123 9
Converted to High
Speed:
0123 5355 5555 7
Normal
4/2 Out
High Speed
In High Speed mode,
messages with event
codes of B and C are
translated to High
Speed Opening and
Closing messages,
respectively.
S/Fast
FBI
LAR300
Extended
Pulse
Extended
Not Extended
A sequence of 1234 B
, BBBB 7 is combined
into a 4-2 message of
1234 B7. (Applies to
B,C,E,F). This mes-
sage would either be
put out to Automation
as 4-2 or High Speed.
When the option is
selected, the receiver
does not combine the
expanded messages.
They are output in the
same form as
received.
High Speed
MX8000
LC1
1 Line
(contd)
Edit Line
(contd)
Line #
(contd)
Ademco
Auto Opt
Extended
Output
4/2
If low speed expanded
messages are
received and
combined (See Pulse
Extended above), the
messages are output
to Automation as 4-2
format messages. For
example, a sequence
of 1234 B , BBBB 7 is
combined and output
as a 4-2 message of
1234 B7.