Item Check That Check Result
The fasteners for the liquid
level detector are secured.
â–¡ Passed â–¡ Failed
The low liquid level detector
functions exibly.
â–¡ Passed â–¡ Failed
Table 4-16 Outdoor unit installation checklist
Item Check Result
The outdoor unit is secured. â–¡ Passed â–¡ Failed
The outdoor unit air intake and
exhaust vents are not blocked.
â–¡ Passed â–¡ Failed
The outdoor unit installation meets
requirements in 4.2.6.3.2 Space
Requirements.
â–¡ Passed â–¡ Failed
Table 4-17 Pipe connection checklist
Item
Check Result
Pipe connectors are correct. The
refrigerant pipe tilts and has supports.
â–¡ Passed â–¡ Failed
The hose clamps and cable ties of the
drainpipe are secured.
â–¡ Passed â–¡ Failed
The refrigerant pipe and water pipe
are wrapped with thermal insulation
foam.
â–¡ Passed â–¡ Failed
All pipes have been checked for leaks. â–¡ Passed â–¡ Failed
Water pipe joints have been sealed by
sealant.
â–¡ Passed â–¡ Failed
The pipes are not bent by a large
angle.
â–¡ Passed â–¡ Failed
Stop valves for the gas pipe and liquid
pipe of the outdoor unit are open.
â–¡ Passed â–¡ Failed
Cable holes in walls are sealed. â–¡ Passed â–¡ Failed
FusionModule800 Smart Small Data Center
User Manual 4 Installation Guide