NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
5 Controller Operate Guide
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
standby precision air conditioners to
work alternatively, maximizing
their service life.
when the heat distribution is
even.
Forced rotation specifies whether
to enable a forcible rotation on the
group before the specified rotation
time is satisfied. After a forced
rotation, the accumulative Rotation
time is set to 0.
This function is set to No by
default.
Enable or disable the master device
to send the requirement control for
the slave devices. If set to Enable,
the master device will synchronize
data to the slave device. For
otherwise, set to Disable.
When the T/H control type, temp
set point and humidity set point
have the same values and devices
and heat are distributed evenly,
this function is recommended.
After the requirement control is
enabled, you can configure
Cascade. The cascade function
starts standby NetCol5000-C(s) if
the active one cannot meet the
refrigerating requirements.
If the heat load increases, the
cascade function is
recommended.
Teamwork Information
After all parameters are set, click at the right corner of the main page. Figure 5-42 and
Figure 5-43 will be displayed.
Figure 5-42 Teamwork information page 1