EasyManua.ls Logo

IDEC FL1E-H12RCE

IDEC FL1E-H12RCE
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IDEC SmartRelay functions
IDEC SmartRelay Manual 141
Parameters TH and TL
Note the information on parameter T in Chapter 4.3.2.
The pulse width TH and the interpulse width TL can be
provided b
y the actual value of another already-programmed
function. You can use the actual values of the following
functions:
Analog comparator (actual value Ax - Ay, see Chapter
4.4.18)
Analog trigger (actual value Ax, see Chapter 4.4.16)
Analog amplifier (actual value Ax, see Chapter 4.4.20)
Analog multiplexer (actual value AQ, see Chapter 4.4.26)
Analog ramp control (actual value AQ, see Chapter
4.4.27)
Analog math (actual value AQ, see Chapter 4.4.30)
PI controller (actual value AQ, see Chapter 4.4.28)
Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. The
timebase is conf
igurable. For information on valid ranges
and parameter defaults, refer to Chapter 4.4.1.
Trg
T
a
is running
Q
T
H
T
H
N=1
T
L
=0
The bold section of the
timing diagram also
appears in the symbol of
the edge-triggered
interval time-delay relay.
Trg
N=2
Q
T
L
T
H
T
L
T
H
T
L
T
H
T
L
T
H
Timing diagram for the sample
configuration
Timing diagram A
Timing diagram B
Functional description
A 0 to 1 transition at input Trg triggers the time T
L
(Time
Low). After the time T
L
has expired, output Q is set for the
duration of T
H
(Time High).
If there is a further 0 to 1 transition (retrig
gering pulse) at
input Trg before the preset time (T
L
+ T
H
) has expired, T
a
is
reset and the pulse/pause cycle is restarted.
If retentivity is not set, output Q and the time are reset after
a power failure.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Related product manuals