IDEC SmartRelay functions
IDEC SmartRelay Manual 179
Setting the Par parameter
The gain and offset parameters are used to adapt the
sensors to the relevant application.
View in programming mode:
B3 1+
On =+00000
Off =+00000
Parameter protection mode
On threshold
Off threshold
Press
B3 2
A =00.00
B =+00000
p=0
Gain
Offset
Decimals in the message text
Example
In a heating control system, the supply T
v
and return line
temperatures T
r
are to be compared, for example with a
sensor at AI2.
A control signal is to be triggered (for example ”heater On”)
when the
difference between the supply and return line
temperatures is greater than 15. The control signal is reset
when the diffe
rence is less than 5C.
The process variable of the temperature is to be shown in
parameter a
ssignment mode.
The thermocouples available have the the following
technical data: -30 to +70C, 0 to 10 VDC.
Application Internal mapping
-30 to +70
C = 0 to 10 V DC 0 to 1000
0 C300
Offset = -30
Range of values:
-30 to +70
C = 100
1000
Gain = 100/1000 = 0.1
On threshold = 15 C Threshold = 15
Off threshold = 5
C Threshold = 5
See also Chapter 4.3.6.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC FL1E-H12RCE and is the answer not in the manual?

IDEC FL1E-H12RCE Specifications

General IconGeneral
BrandIDEC
ModelFL1E-H12RCE
CategoryOther
LanguageEnglish

Related product manuals