Parameter Groups
‑141‑
F3-16
Voltage decline time of V/f separation
Address:
0xF310
Min.:
0
Unit:
s
Max.: 1000 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 1000.0s
Description
Indicates the time required for the output voltage to decline from the set V/f
separation voltage to 0.
F3-17
Stop mode selection for V/f separation
Address:
0xF311
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Frequency and voltage decline to 0.
1: Frequency declines to 0 after voltage declines to 0.
Description
0: Frequency and voltage decline to 0.
1: Frequency declines after voltage declines to 0.
F3-18
V/f overcurrent stall action current
Address:
0xF312
Min.:
50
Unit:
%
Max.: 200 Data type: UInt16
Default:
150
Change:
At stop
Value Range:
50% to 200%
Description
When the motor current reaches the value of this parameter, the AC drive starts
the overcurrent stall function. The default value is 150%, indicating 1.5 times the
rated current of the AC drive.
F3-19
V/f overcurrent stall
Address:
0xF313
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
1
Change:
At stop
Value Range: