Function Application
‑582‑
In speed control mode, if F2‑11 is set to 1 to 8, the torque upper limit is distinguished
between the motoring state and generating state. In motoring state, the full range of
torque upper limit is set through F2‑10. In generating state, the full range of torque
upper limit is set through F2‑12.
Figure 3‑45 Torque upper limit in speed control mode
Para. No. Function Default
Value Range Description
F2‑53
Power limit selection during
generating
0
0: Disabled
1: Enabled
‑
F2‑54
Power upper limit during generating Model dependent
0.0% to 200.0% ‑
In applications such as cam, quick acceleration/deceleration and sudden unloading
without using a braking resistor, enable the power limit during generating to reduce
bus voltage overshoot during motor braking so as to prevent overvoltage. F2‑54
(power upper limit during generating) is a percentage to the rated motor power. If
overvoltage still occurs after power limit during generating is enabled, decrease F2‑
54.
3.4.8 Torque Control
Para.
Function
Default Value Range
Description
A0‑00
Speed/Torque
control mode
0
0: Speed control
1: Torque control
In FVC or SVC mode, speed
control and torque control
modes are available.
A0‑01
Torque reference
source
0
0: Digital setting
(A0‑03)
1: AI1
2: AI2
3: AI3
4: Pulse reference
5:
Communication
(1000H)
6: Min. (AI1, AI2)
7: Max. (AI1, AI2)
This parameter is used to
set the torque setting
command source. Eight
torque setting channels are
available.