Parameter Groups
382
Min.:
10
Unit:
Max.: 1000 Data type: UInt16
Default:
100
Change: In real time
Value Range:
10 to 1000
Description
2.22 AC AI/AO Correction
AC-00
AI1 measured voltage 1
Address:
0xAC00
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
2
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description
When analog voltage correction is conducted on AI1, a correction curve is
obtained based on two points. Each point corresponds to a measured voltage and
a displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the AI1 voltage before correction (U0‑21).
AC-01
AI1 displayed voltage 1
Address:
0xAC01
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
2
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description
When analog voltage correction is conducted on AI1, a correction curve is
obtained based on two points. Each point corresponds to a measured voltage and
a displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the AI1 voltage before correction (U0‑21).
AC-02
AI1 measured voltage 2
Address:
0xAC02
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16