Function Application
606
Step
Forward jog
Reverse jog
3
Set F8‑00 (jog frequency), F8‑01 (jog
acceleration time), and F8‑02 (jog
deceleration time) properly.
Set F8‑00 (jog frequency), F8‑01 (jog
acceleration time), and F8‑02 (jog
deceleration time) properly.
4
In stop status, when the MF.K key is
pressed down, the AC drive starts to
jog in the forward direction. When
the MF.K key is released, the AC
drive decelerates to stop.
In stop status, when the MF.K key is
pressed down, the AC drive starts to
jog in the forward direction. When
the MF.K key is released, the AC
drive decelerates to stop.
3.5.2 Frequency Detection
3.5.2.1 Multi-Speed Reference
In multi‑reference mode, combinations of different DI terminal states correspond to
different frequency references.
Table 3–31 Procedure of configuring multi‑speed as frequency reference
Procedure Para.
Description
Step 1: Select multi‑speed as the
frequency reference.
F0‑03 Set F0‑03 to 6.
Step 2: Set the quantity of
references.
None.
A maximum of 16 references are supported, requiring four DI
terminals. The relationship between the reference quantity and DI
terminal quantity is as follows:
Two references: one DI terminal K1
Three to four references: two DI terminals K1 and K2
Five to eight references: three DI terminals K1, K2, and K3
Nine to sixteen references: four DI terminals K1, K2, K3, and K4
Step 3: Set the multi‑speed function
for DI terminals.
F4‑00 to F4‑09
Multi‑reference terminal K1: Set to 12
Multi‑reference terminal K2: Set to 13
Multi‑reference terminal K3: Set to 14
Multi‑reference terminal K4: Set to 15
Step 4: Set the frequency for each
reference
[Note]
FC‑00 to FC‑15
Set the frequency for each reference, in percentage. 100%
corresponds to max. frequency F0‑10.
F0‑10
When frequency reference is set to multi‑speed, 100% of the
parameters FC‑00 to FC‑15 corresponds to max. frequency F0‑10.
[Note] The four multi‑reference terminals can make up 16 state combinations,
corresponding to 16 frequency reference values, as listed in the following table.
Table 3–32 Combinations of multi‑speed terminals
K4 K3 K2 K1 Reference
Max. Frequency (%)
OFF OFF OFF OFF Multi‑reference 0 FC‑00
OFF OFF OFF ON Multi‑reference 1 FC‑01