Function Application
‑617‑
Figure 3‑68 Timing diagram of detection level of current
Related parameters
Para.
No.
Function Default
Value Range Description
F8‑38
Detection level of
current 1
100.0%
0.0% to 300.0% (rated
motor current)
The DO terminal outputs the active signal when the
output current of the AC drive is in the range of F8‑
38±F8‑39 x F1‑03, where F8‑38 is detection level of
current 1, F8‑39 is detection width of current 1, and F1‑
03 is rated motor current.
F8‑39
Detection width of
current 1
0.0%
0.0% to 300.0% (rated
motor current)
Numeric value of detection width of current 1 = F8‑39
(detection width of current 1) x F1‑03 (rated motor
current)
F8‑40
Detection level of
current 2
100.0%
0.0% to 300.0% (rated
motor current)
The DO terminal outputs the active signal when the
output current of the AC drive is in the range of (F8‑
40±F8‑39) x F1‑03, where F8‑40 is detection level of
current 2, F8‑39 is detection width of current 1, and F1‑
03 is rated motor current.
F8‑41
Detection width of
current 2
0.0%
0.0% to 300.0% (rated
motor current)
Numeric value of detection width of current 2 = F8‑41
(detection width of current 2) x F1‑03 (rated motor
current)
3.5.4 Forward/Reverse Run Switchover Dead Zone Time
This function is used to specify the transition period when the output is 0 Hz during
forward/reverse run switchover of the AC drive. The transition period is called
forward/reverse run switchover dead zone time, which can be set through F8‑12.