Parameter Groups
‑364‑
Description
This parameter defines the jump amplitude set through AI3.
A6-30
Analog disconnection detection
Address:
0xA61E
Min.:
0
Unit:
‑
Max.: 111 Data type: UInt16
Default:
0
Change: In real time
Value Range:
Ones position: AI1 disconnection detection
0: Disabled
1: Enabled
Tens position: AI2 disconnection detection
0: Disabled
1: Enabled
Hundreds position: AI3 disconnection detection
0: Disabled
1: Enabled
Description
After AI1 disconnection detection is enabled, when the voltage detected at AI1 is
lower than the threshold set by A6‑22 for over the time set by A6‑23, the AC drive
reports fault E48.01.
After AI2 disconnection detection is enabled, when the voltage detected at AI2 is
lower than the threshold set by A6‑22 for over the time set by A6‑23, the AC drive
reports fault E48.02.
After AI3 disconnection detection is enabled, when the voltage detected at AI3 is
lower than the threshold set by A6‑22 for over the time set by A6‑23, the AC drive
reports fault E48.03.
2.21 A9 Vector Control Supplementary Parameters
A9-00
Online auto-tuning of rotor time constant for asynchronous motors
Address:
0xA900
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled