Function Application
‑511‑
K4 K3 K2 K1
Reference Corresponding
Parameter
OFF OFF ON OFF
Multi‑reference
2
FC‑02
OFF OFF ON ON
Multi‑reference
3
FC‑03
OFF ON OFF OFF
Multi‑reference
4
FC‑04
OFF ON OFF ON
Multi‑reference
5
FC‑05
OFF ON ON OFF
Multi‑reference
6
FC‑06
OFF ON ON ON
Multi‑reference
7
FC‑07
ON OFF OFF OFF
Multi‑reference
8
FC‑08
ON OFF OFF ON
Multi‑reference
9
FC‑09
ON OFF ON OFF
Multi‑reference
10
FC‑10
ON OFF ON ON
Multi‑reference
11
FC‑11
ON ON OFF OFF
Multi‑reference
12
FC‑12
ON ON OFF ON
Multi‑reference
13
FC‑13
ON ON ON OFF
Multi‑reference
14
FC‑14
ON ON ON ON
Multi‑reference
15
FC‑15
3.1.2.6 Setting the Main Frequency Through Simple PLC
Step 1: Set F0‑03 to 7 to select simple PLC as the main frequency reference.
Step 2: Set parameters FC‑00...FC‑15 and FC‑18...FC‑49 to define the running time and
acceleration/deceleration time for each reference.