Parameter List
‑88‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
B6‑98 0xB662 Write gain 25 0.00–100.00 0 ‑ In real time "
B6‑98
"
on
page 468
B6‑99 0xB663 Read gain 25 0.00–100.00 0 ‑ In real time "
B6‑99
"
on
page 468
1.2 List of Monitoring Parameters
Table 1–1 Monitoring parameters
Parameter Name Basic Unit Communication
Address
Group U0: basic monitoring parameters
U0‑00 Running frequency (Hz) 0.01 Hz 0x7000
U0‑01 Frequency reference (Hz) 0.01 Hz 0x7001
U0‑02 Bus voltage (V) 0.1 V 0x7002
U0‑03 Output voltage (V) 1 V 0x7003
U0‑04 Output current (A) 0.1 A 0x7004
U0‑05 Output power (kW) 0.1 kW 0x7005
U0‑06 Output torque (%) 0.1% 0x7006
U0‑07 DI state 1 0x7007
U0‑08 DO state 1 0x7008
U0‑09 AI1 voltage (V) 0.01 V 0x7009
U0‑10 AI2 voltage (V) 0.01 V 0x700A
U0‑11 AI3 voltage (V) 0.01 V 0x700B
U0‑12 Count value 1 0x700C
U0‑13 Length value 1 0x700D
U0‑14 Load speed display 1 0x700E
U0‑15 PID reference 1 0x700F
U0‑16 PID feedback 1 0x7010
U0‑17 PLC stage 1 0x7011
U0‑18 Pulse input reference (kHz) 0.01 kHz 0x7012
U0‑19 Feedback speed (Hz) 0.01 Hz 0x7013
U0‑20 Remaining running time 0.1 min 0x7014
U0‑21 AI1 voltage before correction 0.001 V 0x7015
U0‑22 AI2 voltage (V)/current (mA) before
correction
0.001 V 0x7016
U0‑23 AI3 voltage before correction 0.001 V 0x7017
U0‑24 Linear speed 1 m/min 0x7018
U0‑25 Current power‑on time 1 min 0x7019
U0‑26 Current running time 0.1 min 0x701A