EasyManua.ls Logo

Inovance MD500-PLUS Series - Current Detection; Zero Current Detection; Output Current Limit Violation

Inovance MD500-PLUS Series
718 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Application
‑615‑
3.5.3 Current Detection
3.5.3.1 Zero Current Detection
The DO outputs the active signal when the output current of the AC drive remains at
or below F8‑34 (zero current detection level) for a period greater than the value of F8‑
35 (zero current detection delay).
Figure 3‑66 Zero current detection
Related parameters
Para. No. Function Default
Value Range Description
F8‑34
Zero current detection
level
5.0%
0.0% to 300.0% (rated
motor current)
The DO outputs the active
signal when the output current
of the AC drive remains at or
below F8‑34 (zero current
detection level) for a period
greater than the value of F8‑35
(zero current detection delay).
F8‑35
Zero current detection
delay
0.10s 0.00s to 600.00s
3.5.3.2 Output Current Limit Violation
The DO terminal outputs the active signal when the output current of the AC drive
remains above F8‑36 (output limit violation threshold) for a period greater than the
value of F8‑37 (output overcurrent detection delay).

Table of Contents

Other manuals for Inovance MD500-PLUS Series

Related product manuals