Parameter Groups
268
Value Range:
0100
Description
This parameter is valid only in the "keep bus voltage constant" mode (F9‑59 = 2).
If undervoltage occurs frequently during power dip ride‑through, increase the
power dip ride‑through gain and integral coefficient.
F9-73
Deceleration time of power dip ride-through
Address:
0xF949
Min.:
0
Unit:
s
Max.: 300 Data type: UInt16
Default:
20
Change: In real time
Value Range:
0.0s to 300.0s
Description
This parameter is valid only in the "decelerate to stop" mode (F9‑59 = 2).
When the bus voltage is lower than the value of F9‑62, the AC drive decelerates to
stop. The deceleration time is determined by this parameter instead of F0‑18.
2.11 FA Process Control PID
FA-00
PID reference source
Address:
0xFA00
Min.:
0
Unit:
Max.: 6 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: PID digital setting (FA‑01)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication setting (1000H)
6: Multi‑reference
Description
This parameter specifies the PID reference source. The PID reference source is a
relative value. The value 100% corresponds to 100% of the feedback signal of the
controlled system.
0: PID digital setting of (FA‑01)
The PID reference source is set by FA‑01 (PID reference value).