2 Parameter Groups
2.1 F0 Basic Parameter Group
F0-00
G/P type display
Address:
0xF000
Min.:
1
Unit:
Max.: 2 Data type: UInt16
Default:
1
Change:
At stop
Value Range:
1: G type (constant‑torque load)
2: P type (fan and pump)
Description
1: G type (constant‑torque load)
The G type models typically carry constant‑torque loads with large overload
capacity. The overload capacity is 150% in general. Such loads include conveyor
belts and cranes, for example.
2: P type (fan and pump)
The P type models typically carry variable‑torque loads such as fan and water
pump.
F0-01
Motor 1 control mode
Address:
0xF001
Min.:
0
Unit:
Max.: 5 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Sensorless vector control (SVC)
1: Feedback vector control (FVC)
2: V/f control
3: Reserved
4: Reserved
5: Speed open loop control for the synchronous motor (PMVVC)
Description
0: Sensorless vector control (SVC)
It is a type of open‑loop vector control applicable to high‑performance control
applications, where one AC drive can drive only one motor. It is used for loads
such as machine tools, centrifuges, wire drawing machines, and injection molding
machines.