Function Application
‑687‑
Para.
Function Basic Unit Description
U0‑75 Torque
reference after
acceleration/
deceleration
0.1%
Torque reference after acceleration/
deceleration in torque control mode
U0‑76 Torque upper
limit in the
motoring state
0.1%
The torque upper limit under the motoring
state takes the rated current of the AC drive as
the base value.
U0‑77 Torque upper
limit in the
generating state
0.01%
The torque upper limit under the generating
state takes the rated current of the AC drive as
the base value.
3.9 User Settings
3.9.1 User-Defined Parameters
Group FE consisting of parameters FE‑00 to FE‑29) is used to define frequently‑used
parameters to facilitate operations such as viewing and modification. Up to 30 user‑
defined parameters can be set.
If the displayed value is F0‑00, no parameter is defined. In the user‑defined
parameter mode, you can use FE‑00 to FE‑31 in sequence to define which
parameters to display and skip any parameter by setting the value to F0‑00.
Displayed values U3‑17 and U3‑16 indicate PZD1 (AC drive command word) in
communication control and PZD2 (AC drive target frequency) in communication
control, respectively.