Parameter Groups
‑207‑
F5-22
DO active mode selection
Address:
0xF516
Min.:
0
Unit:
Max.: 11111 Data type: UInt16
Default:
0
Change: In real time
Value Range:
Ones (position): Expansion card relay
0: Positive logic
1: Negative logic
Tens (position): Control board relay 1
0: Positive logic
1: Negative logic
Hundreds (position): Control board relay 2
0: Positive logic
1: Negative logic
Thousands (position): Control board DO1
0: Positive logic
1: Negative logic
Ten thousands (position): Extension card DO2
0: Positive logic
1: Negative logic
Description
The ones, tens, hundreds, thousands, and ten thousands positions of this
parameter are used to set the DOs to which F5‑01 to F5‑05 correspond.
0: Positive logic (same as NO contact)
Active state: The DO and the COM/ CME terminal are internally connected.
Inactive state: The DO terminal is disconnected from the COM/CME terminal.
1: Negative logic (same as NC contact)
Active state The DO terminal is disconnected from the COM/CME terminal.
Inactive state: The DO terminal and the COM/CME terminal are internally
connected.
2.7 F6 Start/Stop Control
F6-00
Start mode
Address:
0xF600
Min.:
0
Unit:
Max.: 2 Data type: UInt16
Default:
0
Change: In real time
Value Range: