Parameter Groups
‑322‑
Description
This parameter is used to determine whether the user‑customized parameter
group and the user‑modified parameter group are displayed on the operating
panel.
FP-04
Parameter modification property
Address:
0x1F04
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Modification allowed
1: Modification prohibited
Description
Used to determine whether the parameters can be modified.
2.17 A0 Torque Control and Restricting Parameters
A0-00
Speed/Torque control mode
Address:
0xA000
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Speed control
1: Torque control
Description
Two control modes, speed control and torque control, are provided under vector
control (FVC or SVC).
A0-01
Torque setting source selection
Address:
0xA001
Min.:
0
Unit:
‑
Max.: 7 Data type: UInt16
Default:
0
Change:
At stop
Value Range: