Parameter Groups
‑321‑
4: Back up current user parameters
The current parameter settings are backed up.
501: Restore user backup parameters
Parameters backed up by setting FP‑01 to 4 are restored.
503: Restore to factory parameter mode 2
All AC drive parameters, excluding manufacturer parameters in group FF, FP‑00,
and FP‑01, are restore to default settings.
FP-02
Parameter display selection
Address:
0x1F02
Min.:
0
Unit:
Max.: 1111 Data type: UInt16
Default:
111
Change: In real time
Value Range:
Ones position: Group U
0: Hide
1: Display
Tens position: Group A
0: Hide
1: Display
Hundreds position: Group B
0: Hide
1: Display
Thousands position: Reserved
Description
This parameter is used to determine whether the parameters of groups U, A, B,
and C are displayed on the operating panel.
FP-03
Display selection of customized parameters
Address:
0x1F03
Min.:
0
Unit:
Max.: 11 Data type: UInt16
Default:
11
Change: In real time
Value Range:
Ones (position): Display of user‑defined parameter groups
0: Hide
1: Display
Tens (position): Display of user‑modified parameter groups
0: Hide
1: Display